Product Overview
This 500kVA dry type transformer is custom-engineered for the Vietnamese power grid. The design integrates specialized winding configurations for optimized operational efficiency, digital thermal monitoring for precise temperature control, and localized dampening features for low-noise performance.
Application & Selection Guide
1. 500 kVA Dry-Type Transformer Application Scenarios & Key Advantages
| Target Environment / Scenario | Specific Application Site | Technical Features |
|---|---|---|
| High-Density Public Spaces | Shopping malls, hospitals, schools | Minimized Fire Risk: Oil-free solid insulation meets stringent indoor fire safety standards. |
| Space-Constrained Facilities | High-rise office basements, apartment mezzanines | Compact Footprint: Lightweight design allows installation in confined rooms. |
| Humid & Corrosive Zones | Coastal underground complexes, chemical workshop auxiliaries | Moisture Resistance: Sealed insulation prevents degradation from high humidity. |
| Noise-Sensitive Facilities | R&D laboratories, biopharmaceutical buildings, hotels | Acoustic Mitigation: Shock-absorbing spring pads dampen core resonance. |
| Restricted-Access Zones | Data center server rooms, subway station control rooms | Maintenance-Free: Solid-state structure eliminates routine oil testing. |
2. Why Dry-Type Transformers Are Ideal for Indoor Use?
Compared to oil-immersed transformers, the dry-type (cast resin) design offers distinct safety, environmental, and installation advantages that make it the preferred choice for indoor and sensitive environments:
| Advantage | Detailed Benefit for Indoor Use |
|---|---|
| Enhanced Fire Safety | Oil-free solid insulation is self-extinguishing and has no flammable liquid, significantly reducing fire risk and meeting stringent indoor fire safety codes (ideal for basements, high-rises). |
| Environmentally Friendly | No risk of oil leaks, eliminating potential soil or groundwater contamination. Safe for use in environmentally regulated areas. |
| Compact Installation | Generally lighter and more compact than oil-filled units for the same capacity, allowing for easier handling and installation in space-constrained indoor electrical rooms. |
| Low Maintenance | Solid-state structure eliminates the need for regular oil quality testing, oil level checks, and oil filtration, drastically reducing routine maintenance effort and cost. |
| Low Noise Level | Designed with advanced materials and damping features, it operates more quietly, making it suitable for noise-sensitive environments like hospitals, hotels, and office areas. |
3. Temperature Monitoring & Maintenance Approach
Temperature Monitoring:This 500 kVA dry-type transformer is equipped with a digital thermal monitoring system for precise and continuous temperature control. Key aspects include:
Real-Time Monitoring :Sensors embedded in the windings provide continuous temperature readings, ensuring the unit operates within safe thermal limits (Class F/H insulation).
Alarm & Trip Functions :The system can be configured with programmable alarm and trip thresholds. If temperatures exceed preset levels, it triggers an alert or automatically shuts down the transformer to prevent insulation damage from overheating.
Fan Control :For units with forced air cooling (ANAF), the system can automatically control cooling fans, activating them when temperatures rise and deactivating them when temperatures drop, optimizing energy efficiency.
Maintenance Approach :The "maintenance-free" nature of dry-type transformers significantly simplifies upkeep:
Regular Visual Inspection :Periodically inspect for any unusual dust accumulation, physical damage, or signs of overheating on the enclosure and connections.
Clean Cooling Vents :Keep air intake and exhaust vents clear of debris to ensure proper ventilation and cooling efficiency.
Check Fan Operation :If equipped with fans, verify they start and stop correctly based on temperature signals during routine checks.
Periodic Electrical Testing:While routine oil testing is unnecessary, it is recommended to perform periodic insulation resistance and partial discharge measurements to track insulation system health.
4. Real-World Application Cases
A Data Center Server Room
A colocation data center needed a reliable, fire-safe power source for its server racks and cooling systems. They deployed a 500kVA dry-type transformer in a dedicated electrical room adjacent to the server hall. The solid-state, oil-free design eliminated the risk of a transformer fire affecting the critical IT load. The maintenance-free operation reduced the need for regular human intervention, aligning with the facility's high-reliability and security protocols.
Scope of Supply
Product: Cast resin type transformer
Number of phases: Three-phase
Rated Capacity: 500 kVA (Custom options available from 30 kVA to 3150 kVA upon request)
Primary voltage: 10,000V
Secondary voltage: 400V
Frequency: 50Hz
Vector Group: Dyn11
Customizable production: Available
Technical Specifications
|
Model |
SCB10-500kVA-10/0.4 |
|
Type |
Dry type Transforme |
|
Standard |
IEC60076 |
|
Rated Power |
500kVA |
|
Frequency |
50HZ |
|
Phase |
Three |
|
Cooling Type |
ANAF |
|
Primary Voltage |
10 KV |
|
Secondary Voltage |
0.4KV |
|
Winding Material |
Copper |
|
Vector Group |
Dyn11 |
|
Impedance |
4% |
|
Tap Changer |
NLTC |
|
Tapping Range |
±2*2.5% @ Primary Side |
|
No Load Loss |
1.16 KW |
|
On Load Loss |
4.88KW |
Compliance & Technical Standards
✔ IEC 60076-11 Verification
Restricts routine partial discharge to ≤ 10 pC while ensuring compliance with Class F/H insulation thermal limits.
✔ ISO 9001 Audited Winding Process
Utilizes automated foil-winding equipment to ensure precise interlayer tension and eliminate internal voids.
✔ IP20 / IP23 Enclosure Compliance
Validated clearance design and ingress protection prevent hazardous particle intrusion in indoor substations.
✔ Pre-Dispatch Factory Testing
Each unit undergoes mandatory AC withstand test (28 kV / 1 min), insulation resistance measurement, and loss performance verification.
System Engineering Design

Engineering Drawings & Schematics

Manufacturing Process & Quality Control
Resin Casting Process Flow (Dry-Type Coils):
Preliminary preparation
Mold installation
Pouring operation
Curing treatment
Demoulding and trimming
Quality Control & Testing:
1. Clean-Room Coil Casting
Environmental particulate monitoring (< Class 100,000 cleanroom standards) mitigates micro-void encapsulation during vacuum resin injection to maintain partial discharge thresholds under ≤ 10 pC at 1.3Uₙ.
2. Multi-Zone Thermal Curing
Automated temperature regulation ensures uniform resin polymerization, preventing cracks and enhancing mechanical stability.
3. Dielectric Impulse Verification
Mandatory 28 kV AC withstand testing verifies high-voltage insulation strength before factory dispatch.
4. Short-Circuit Resistance Testing
Structural tolerance validation confirms that encapsulated copper coils can withstand severe grid short-circuit stresses.






FAQ
Q: Are type test reports available for this 500kVA transformer design?
A: Yes. The design is fully validated according to IEC 60076-11. Complete KEMA type test reports-including temperature rise, lightning impulse (BIL), and short-circuit withstand tests-are available upon request.
Q: How does the factory guarantee core laminations are protected from rust during seaside transit?
A: Cores receive a specialized multi-layer anti-corrosive marine varnish coating prior to sea-freight packaging.
Q: What heavy-duty logistics measures prevent internal structural shifting during overland delivery?
A: Transformers are secured using heavy-duty internal bracing and multi-point tie-downs within custom wood crates.
Q: Can the enclosure configuration be upgraded to withstand outdoor industrial dust environments?
A: Yes, the standard enclosure can be upgraded to IP23 or IP44 rated stainless steel structures.
Hot Tags: 500kva dry type transformer, China 500kva dry type transformer manufacturers, suppliers, factory, cast coil transformer, 50 kva dry type transformer, dry type cast resin, transformer dry, medium voltage dry type transformers, 33kv dry type transformer