Product Introduction
This 11kV/415V, 50Hz oil-immersed three phase 500kVA transformer is engineered to comply with Nigerian distribution network standards, supporting stable power step-down under high-ambient tropical conditions.
Scope of Supply
Product Category: Liquid-Immersed Distribution Transformer
Phase Configuration: Three-Phase
Rated Capacity: 500 kVA
Primary Voltage: 11KV
Secondary Voltage: 415V
Vector Group: Dyn11
Customizable Production: Yes
Key Advantages
- Thermal Overload Resilience: Optimized radiator oil-convection channels and high-flashpoint mineral insulation oil sustain short-term cyclic overloads during regional peak demand spikes.
- Extended Voltage Regulation: Configured with a ±2×2.5% off-circuit tap changer (NLTC) to counteract local grid voltage drops.
- Harmonic Distortion Tolerance: Reinforced mechanical winding clamping and core mitering mitigate magnetic flux distortion and vibration caused by non-linear industrial loads.
Applications
| Application | System Integration | Primary Benefit |
|---|---|---|
| Power Utilities | Grid distribution and local substations | Minimizes no-load core losses |
| Heavy Industry | Manufacturing and chemical plant processing | High short-circuit thermal withstand capacity |
| Transportation | Rail, airports, and seaport infrastructure | Sustains heavy cyclic loading profiles |
| Commercial Buildings | Data centers, hospitals, and residential areas | High heat dissipation under high-density loads |
| Renewable Energy | Photovoltaic and wind grid-tie systems | Mitigates non-linear harmonic distortion |
Technical Specifications
|
Model |
S-M-500kVA-11/0.415 |
|
Type |
Oil Immersed Power Transformer |
|
Standard |
IEC60076 |
|
Rated Power |
500kVA |
|
Frequency |
50HZ |
|
Phase |
Three |
|
Cooling Type |
ANAF |
|
Primary Voltage |
11 KV |
|
Secondary Voltage |
0.415KV |
|
Winding Material |
aluminium |
|
Vector Group |
Dyn11 |
|
Impedance |
4% |
|
Tap Changer |
NLTC |
|
Tapping Range |
±2*2.5% @ Primary Side |
|
No Load Loss |
0.680 KW |
|
On Load Loss |
5.41KW |
|
Accessories |
Standard Configuration |
System Engineering Design

Engineering Workflow:
| Phase 1: Drawing Design - Engineers design tailored electrical and structural schematics. |
| Phase 2: Iron Core Production - Silicon steel sheets cut and stacked precisely. |
| Phase 3: Winding Production - Automated machines wind high and low-voltage coils. |
| Phase 4: Tank Production - Steel enclosures are fabricated, welded, and sealed. |
| Phase 5: Customized Accessories Preparation - Bushings, radiators, and tap changers inspected. |
| Phase 6: Transformer Assembly - Core, windings, and tank fully integrated. |
| Phase 7: Experimental Testing - Units undergo full routine electrical testing. |
| Phase 8: Packaging & Shipping - Transformers are dried, sealed, and securely packaged. |
Engineering Drawings & Schematics

Iron Core
Coil Winding
Transformer assembly
Transformer Tank


FAQ
Q: What quality documentation is provided before this Three Phase 500 Kva Transformer ships?
A: Each unit ships with a certified Factory Acceptance Test (FAT) report covering routine dielectric and loss measurements.
Q: How is this Three Phase 500 Kva Transformer protected against moisture during ocean transit?
A: Transformers are vacuum-dried, nitrogen-sealed, and packed in heavy-duty seaworthy wooden cases with moisture-absorbent desiccants.
Hot Tags: three phase 500 kva transformer, China three phase 500 kva transformer manufacturers, suppliers, factory, phase transformer, single phase variable transformer, three phase step up transformer, delta wye three phase transformer, 50 kva single phase transformer amps, dry and oil type transformer